+86 13938808058 sales@jianyuncable.com
Solar Cable
Solar Cable

Solar cables are an essential component of solar photovoltaic (PV) systems, which convert sunlight into electricity. They are specifically designed to handle the demanding conditions found in solar installations, including exposure to UV rays, high temperatures, and moisture.

Home / Product / Solar Cable / Red/Black 50mm² H1Z2Z2-K Solar Cable (0.6/1kV)

Red/Black 50mm² H1Z2Z2-K Solar Cable (0.6/1kV)

Red/Black 50mm² H1Z2Z2-K Solar Cable (0.6/1kV)

RNEDA Single Core 50mm2 H1Z2Z2-K Solar Cable Red and Black 0.6/1kV AC / for Meter Price in China

  • Details

Key Product Specifications

Attribute

Detail

Product Name

Photovoltaic Wire

Model Number

PV1-F, PV Cable

Common Type

PV, PV1-F, H1Z2Z2-K

Type

Low Voltage

Standard

U L4703 & EN50618 & TUV 2PfG/1169

Voltage

AC $0.6/1\text{ kV}$, DC $0.9/1.5\text{kV}$, Max. $1.8\text{ kV}$ DC

Conductor Material

Copper or Aluminum

Conductor

Flexible Tinned Copper, Bare Copper, Aluminum alloy Conductor

Number of Cores

Single Core or Double Core

Insulation Material

XLPO (Cross-Linked Polyolefin)

Jacket

Low smoke halogen free XLPE

Common Structure

CU(AL)/XLPO, CU(AL)/XLPO/XLPO

Application

Photovoltaic (PV) Solar Power

Certificate

U L, TUV Double certification

Brand and Logistics

Attribute

Detail

Brand Name

JYXL

Place of Origin

Henan, China

Selling Units

Single item

Product Description

Applications:

This cable is used for interconnecting power supplies within renewable energy photovoltaic

systems, such as solar panel arrays in solar energy farms. These solar panel cables are suitable

for fixed installations, both internal and external, and within conduits or systems.

Structure:

1. Conductor: Tinned soft copper wires, class 5, according to EN60228;

2. Insulation: Cross-linked polyolefin, low smoke zero halogen(LSZH)

3. Jacket: Cross-linked polyolefin, low smoke zero halogen(LSZH)

Working temperature:

Max. conductor temperature: 120℃

Ambient temperature: -40 to +90.

Standards:

EN50618

Voltage:

DC 1.5KV, AC1.0/1.0KV

Performance:

Strong UV resistanceFlame retardant

Low smoke halogen free LSZH

Lift time at least 25 years

Test voltage:

AC 6.5KV for 5min, not break down

Techncial Datas:

Conductor Size               (mm2)

Inner Insulation

Outer Insulation

Approx. Nominal Overall Diameter

Nominal Thickness

Nominal Thickness

(mm)

(mm)

(mm)

1x4

0.7

0.8

5.6 

1x6

0.7

0.8

6.3 

1x10

0.7

0.8

7.4 

1x16

0.7

0.9

8.6 

1x25

0.9

1

11.1 

1x35

0.9

1.1

13.0 

1x50

1.0

1.2

15.1 

1x70

1.1

1.2

17.2 

1x95

1.1

1.3

18.6 

1x120

1.2

1.3

20.6 

1x150

1.4

1.4

23.4 

1x185

1.6

1.6

25.5 

1x240

1.7

1.7

28.7 

 