Medium voltage (MV) power cables are essential components in modern electrical power distribution systems, designed to handle voltages ranging from 1kV to 35kV. They serve as the backbone for transmitting electrical energy between substations, transformers, and end-user equipment in both industrial and utility settings.

Home / Product / Medium Voltage Power Cable / MV 1x400mm² Armoured Power Cable (XLPE/AWA)

MV 1x400mm² Armoured Power Cable (XLPE/AWA)

MV 1x400mm² Armoured Power Cable (XLPE/AWA)

Medium Voltage 1x400mm2 Xlpe/cws/cts/pvc/awa/pvc Power Cable

  • Details

Key Attributes:

Attribute

Value

Category

Model Number

YJLV32

Identification

Brand Name

JYXL

Identification

Type

Medium Voltage

Electrical Rating

Application

Power Station

Function

Conductor Material

Aluminum

Construction

Insulation Material

XLPE (Cross-linked Polyethylene)

Construction

Cores

Single core or three cores

Construction

Armour Type

Steel wire armour, steel tape armour, aluminum wire armour

Protection

Jacket

PVC (Polyvinyl Chloride)

Protection

Standard

IEC60502

Compliance

Certificate

CE, UL, KEMA, TUV

Compliance

Place of Origin

Henan, China

Logistics

Selling Units

Single item

Logistics

Packaging Details

Standard export drum or as your request

Logistics

Port of Dispatch

Tianjin port, Qingdao port, Shang hai port

Logistics

Product descriptions

Application:

It is used to transmit and distribute power in power transmission and distribution system of 35kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable and in partial replace of PVC insulated power cable.

Using features:

1. Rated voltage: Uo/U: 26/35kV, 21/35kV, 12/20 kV (24 kV), 8.7/10kV, 8.7/15kV, 6/6kV, 6/10kV.

2. 2. No. of core: Single-core, Three-core.

3. The highest allowed operating temperature of conductor for long-term working is 90oC. In short-circuit (Max. Long-term is no more than 5 seconds). The highest temperature for conductor is no more than 250.

4. D.C Resistance of the conductor complies with the stipulations of GB/T3956-1997.

5. The environment temperature should be no lower than 0 when lay. Otherwise it should be preheated.

6. The cable is laid without horizontal drop limit. The Min. Bending radius of three-core cable should be no smaller than 12 times of cable outer diameter.

7. Working Frequency Voltage Test:.

For cable with Uo of 3.6kV or lower: 2.5Uo+2kV/5min without puncture.
For cable with Uo of 3.6kv~18kV: 3.5Uo/5min without puncture.
For cable with Uo of 21kV and 26 kV: 2.5Uo/30min without puncture.

8. Partial Discharge Test: The discharge volume should be no more than 10pC under 1.73Uo for the cable

 