Home / Product / Bare Conductor / AACSR PHLOX 147.1 Pastel 288 Conductor
NF C34-125 PHLOX 147.1 Pastel 288 AACSR Overhead Conductor
Attribute |
Detail |
Product name |
AACSR Overhead cable |
Model Number |
AACSR OVER HEAD CABLE |
Brand Name |
JYXL |
Type |
low voltage |
Application |
overhead power transmission |
Conductor Material |
Aluminum Alloy Conductor Steel Reinforced |
Conductor |
Aluminum Alloy Conductor Steel Reinforced |
AACSR class |
A, B, C, AZ, AW |
cross section |
Turkety to Brahma |
Insulation Material |
NO INSULATION |
Jacket |
NONE |
Standard |
ASTM, AS, BS, CSA, DIN, IEC, NFC, SS |
Certification |
ISO9001, ISO14001, OASHA8001 |
Temperature range |
90°C |
Heat resistant Temperature |
150°C |
Place of Origin |
Henan, China |
Packaging and Delivery
Attribute |
Detail |
Selling Units |
Single item |
Packaging Details |
Standard export drum for service drop abc cable or as your request |
Port of dispatch |
Tianjin port, Qingdao port, Shanghai port |
Supply Capacity
Attribute |
Detail |
Supply Ability |
500 kilometers per Month service drop abc cable |
1. Application: The AACSR with high strength are used in river crossing conductors, transmission of power through over head ground wires on long span installations against any given resistance of conductor. It can be used as large span conductor, heavy ice wire or overhead communications wire, ground wire. Temperature for continuous use can be up to 90 ℃. Temperature of heat-resistant AACSR can be up to 150 ℃ and above. It has high current carrying capacity.
2. Standards: ASTM, AS, BS, CSA, DIN, IEC, NFC, SS -etc.
(1)Steel part: Zinc- coated steel wires, one or multi-wires concentric stranded
(2)Aluminium alloy part: Aluminium alloy wires, concentric stranded
AACSR is a concentrically stranded conductor composed of one or more layers of 6201 -T81 aluminum alloy wire stranded with a high-strength coated steel core. The core may be single wire or stranded depending on the size.
The proportions of aluminum alloy and steel can be varied to obtain the relation between current carrying capacity and mechanical strength best suited to each application.
Core wire for AACSR is available with Class A, B or C-galvanized; "aluminized" (AZ): or aluminum clad (AW).
Additional corrosion protection is available through the application of grease to the core or infusion of the complete cable with grease.
NFC 34 -125
Designation |
Aluminium |
Steel |
Cross-sectional Area (mm2) |
OD (mm) |
R at 20C (Ohms/km) |
||||
|
Strands |
Wire Diam. (mm) |
Strands |
Wire Diam. (mm) |
Aluminium |
Steel |
Total |
|
|
PHLOX 116.2 |
18 |
2 |
19 |
2 |
56.5 |
59.7 |
116.2 |
14 |
0.591 |
PHLOX 147.1 |
18 |
2.25 |
19 |
2.3 |
71.6 |
75.5 |
147.1 |
15.75 |
0.467 |
PASTEL 147.1 |
30 |
2.25 |
7 |
2.3 |
119.3 |
27.8 |
147.1 |
15.75 |
0.279 |
PHLOX 181.6 |
18 |
2.5 |
19 |
2.5 |
88.4 |
93.3 |
181.6 |
17.5 |
0.378 |
PASTEL 181.6 |
30 |
2.5 |
7 |
2.5 |
147.3 |
34.4 |
181.6 |
17.5 |
0.226 |
PHLOX 228 |
18 |
2.8 |
19 |
2.8 |
110.8 |
117 |
227.8 |
19.6 |
0.3 |
ACSR Robin Penguin Hawk Dove Kingbird Eagle Conductor Bare Overhead Conductor
ACSR Cable Manufacturer for Fox SKunk lion Bear BS EN50182
NF C34-125 PHLOX 147.1 Pastel 288 AACSR Overhead Conductor
ACSR Robin Penguin Hawk Dove Kingbird Eagle Conductor Bare Overhead Conductor