Medium-Voltage Cable in Duct Banks: Why Ampacity Changes—and How to Specify It

Time: 2026-11-25 11:27:27 Source: Henan Province Jianyun Cable Co., Ltd.


Medium-voltage cable ampacity is not a fixed number.

A cable may carry a certain current in open air, another current when directly buried, and a lower allowable current when installed in a crowded underground duct bank. For utilities, data-center campuses, industrial facilities, and infrastructure projects, this difference can affect cable size, route design, project cost, and long-term reliability.

A cable catalog is a useful starting point. But the final ampacity must reflect the actual installation conditions.

Why Catalog Ampacity Is Not Enough

Published cable ampacity values are usually based on defined installation assumptions.

Those assumptions may include a specific ambient temperature, soil thermal condition, burial depth, conductor operating temperature, cable spacing, and number of loaded circuits. If the project conditions change, the allowable current may also change.

For example, a cable installed in a single duct with adequate spacing may dissipate heat more effectively than the same cable installed in a concrete-encased duct bank beside several heavily loaded circuits.

The question is not only, “What cable size is required?”

It is also, “Can the installation route remove the heat generated by that cable?”

What a Duct Bank Changes

A duct bank is a group of conduits installed underground, often surrounded by concrete or placed in a prepared trench. It is commonly used for utility feeders, substations, industrial plants, transportation infrastructure, and large data-center campuses.

Duct banks offer protection, organization, and room for future circuits. However, they can also limit heat dissipation.

When several power circuits operate close together, each cable adds heat to the surrounding installation. The temperature around the cables can increase, reducing the thermal margin available to each circuit.

The cable design, duct-bank layout, and load profile should therefore be reviewed together.

Six Factors That Change Medium-Voltage Cable Ampacity

1. Soil Thermal Resistivity

Soil is part of the cable cooling system.

Dry, rocky, or poorly compacted soil may not transfer heat as effectively as moist, well-prepared backfill. Seasonal changes can also affect soil conditions.

Where the thermal performance of native soil is uncertain, the project may need a defined thermal backfill material or a more conservative cable design.

2. Duct Material and Duct Size

The conduit material and inside diameter affect air circulation, cable pulling conditions, and heat transfer.

A duct that is too small can make installation difficult and reduce the available space around the cable. The selected duct size must allow for the cable outside diameter, pulling equipment, bending requirements, and project installation practice.

The cable supplier should receive the duct size and material as part of the project information.

3. Cable Spacing and Number of Loaded Circuits

Cable circuits installed close together can heat each other.

A single circuit in a duct bank may perform differently from multiple loaded circuits placed in adjacent ducts. Spare ducts may also be included for future expansion, but the design should clearly identify which circuits will operate at the same time.

This information is especially important for projects with several feeders, redundant paths, or phased construction.

4. Burial Depth and Concrete Encasement

Burial depth affects the cable’s thermal path to the surrounding ground.

Concrete encasement provides mechanical protection and a stable duct-bank structure. However, the complete thermal design still depends on duct arrangement, concrete properties, backfill conditions, and the heat generated by operating cables.

Do not assume that deeper burial or concrete encasement will automatically increase ampacity.

5. Ambient Temperature and Load Profile

The cable conductor produces heat according to the actual electrical load.

A feeder operating continuously near its maximum load produces a different thermal condition from a feeder that experiences short-duration peak demand. High ambient temperatures and elevated ground temperatures can further reduce available thermal margin.

The project should state whether the expected load is continuous, intermittent, seasonal, or subject to future expansion.

6. Cable Arrangement and AC Losses

For three-phase single-core cable systems, conductor arrangement matters.

The selected configuration, phase spacing, metallic screen design, bonding method, and accessory selection can affect electrical losses and heating. These items should be designed as part of the complete system.

For high-current applications, the cable layout should be confirmed by the project electrical engineer before procurement.

Single-Core Cable Arrangement Matters

Single-core medium-voltage cable is widely used for high-current feeders, substations, and duct-bank projects.

However, it requires careful installation planning. The three phase conductors may be arranged in trefoil or flat formation depending on the project design, route geometry, available space, and thermal requirements.

The installation must also consider compatible non-magnetic cable cleats, suitable hardware, bending radius, pulling method, and the required spacing between circuits.

A technically correct cable can still underperform if the installed arrangement does not match the intended design.

Common Duct-Bank RFQ Mistakes

Many RFQs provide only the voltage class, conductor material, and cable cross-section.

That information is not always enough to confirm a suitable cable construction or estimate real-world ampacity.

Common omissions include:

  • Number of circuits operating at the same time

  • Duct material and internal diameter

  • Duct-bank drawing or duct arrangement

  • Cable spacing and circuit separation

  • Burial depth and concrete encasement details

  • Native soil or thermal-backfill conditions

  • Maximum ambient and ground temperature

  • Continuous-load and peak-load requirements

  • Required standard and test documentation

  • Future expansion requirements

A complete RFQ helps prevent late changes to conductor size, cable route, or installation layout.


What to Send Your Cable Supplier

For a medium-voltage duct-bank project, provide the following information:

  1. Required voltage class

  2. Conductor material and preferred cross-section

  3. Single-core or three-core cable construction

  4. Required ampacity and expected load profile

  5. Number of circuits and simultaneous operating conditions

  6. Duct material, internal diameter, and duct-bank drawing

  7. Cable arrangement, spacing, and proposed burial depth

  8. Soil condition, thermal backfill, and concrete-encasement details

  9. Installation route, pulling length, and bending limitations

  10. Required standard, test reports, quantity, drum length, and delivery location

These details allow the supplier to recommend a cable construction that matches the actual project environment.

The Bottom Line

Medium-voltage cable ampacity depends on the complete installation system.

In a duct bank, cable size, circuit spacing, soil condition, conduit design, operating load, and installation arrangement all influence thermal performance. Selecting cable from a catalog value alone can create unnecessary cost or insufficient capacity.

Explore Jianyun Cable’s Medium Voltage Power Cable solutions for utility, industrial, critical-infrastructure, and underground-distribution projects.

For a project-specific recommendation, send your duct-bank layout, voltage class, conductor preference, required ampacity, quantity, and delivery location through Jianyun Cable’s inquiry page.